This installation guide provides installation information, drawings, and controller setup
instructions for the Entraguard Silver telephone entry controller. The Entraguard Silver controller may be used alone or may be connected to an access control network of PXL-500 controllers.
For instructions on how to install a postal lock, see the Entraguard Silver Postal Lock Installation
Application Note (P/N: 01964-001).
Note: It is the responsibility of the installation organization to have technically qualified
personnel performing the hardware installation.
Keri Public Statement on the Amazon Key
Keri Systems, Inc. has updated its policy regarding the integration of
We are pleased to inform you that Amazon has now provided official installation
This change reflects our commitment to supporting secure and flexible access solutions
Please note the following:
Keri Systems remains dedicated to providing robust access control solutions.
|
The Entraguard Silver Telephone Entry Enclosure
Note: For information on the optional PXL-500/PXL-510 board, see the PXL-500/PXL-510 Quick Start Guide (P/N 01918-001). For information on the optional PXL-500G-1 board and gate control, see the PXL-500G-1 Quick Start Guide (P/N 01532-001).
• J14 – connects to the postal lock on the controller
• J11 – requires a jumper to enable communication through the internal PC modem
• J19 & J20 – requires jumpers to enable serial communication
• J11, J19, and J20 must all be removed for LAN operation which is only available on new style
controller PCBs
• D32 – unit power ON
• D41 – reversed power/over current indicator
- Red indicates reversed power
- Green indicates over current condition
• D20, D18, D30, D25 – Relay active
• D29 – RS-485 shield connected on master controller
• D4, D5, D6 – RS-232 serial communication activity
There are two means of communication between the master controller and the host PC:
serial RS-232 or LAN.
An RS-232 serial port connection is made by either:
• a direct serial connection (50 feet maximum)
• through an internal PC modem or external modem
• USB to serial converter – uses the Direct to PC serial connection
Notes:
A LAN connection is made using a LAN-520 device connected to J7 on the New Style Entraguard controller. A LAN unit is only required for the primary controller.
For LAN operation, J11, J19, and J20 must be removed.
Please refer to the LAN-520X LAN Port Installation Guide for detailed information on configuring the LAN unit.
Note: LAN connectivity is not supported on the Old Style Controller board.
If you're turning system power on for the first time, certain tasks must be performed prior to setting up the controller in the software. On the Entraguard Silver main board, hold the Reset Button (SW1) down and turn the controller’s power on. After the controller beeps once, indicating the controller’s firmware is ready for programming, release the SW1 button. The LCD on the front panel will display the Reset Menu. From this menu you may perform these tasks: set the controller’s address, clear the controller’s memory, set the microphone volume, and check diagnostics.
Note: If no keys have been selected within 60 seconds, the unit will time out and go directly to the default message. In order to reach the Reset Menu, the unit must be powered up again.
The controller’s address may only be set through the Reset Menu. Once you have performed the necessary steps to reach the Reset Menu as described above. To set the desired operating address for the controller, press 1 on the keypad. The Set Panel Address screen appears on the LCD.
The address range is from 1 to 128. The primary controller must be set to address 1. Other
secondary Entraguard/PXL controllers may be assigned any number from 2 to 128.
If the address shown as Current is correct, you may either enter the same address and press *, or just press * to return to the reset menu. If you do not enter a new address, or enter the same address that is already assigned to this unit, you will need to clear the memory separately (refer to the Clear the Controller’s RAM section, below).
Note: Changing the address of an Entraguard Silver controller completely erases all information within the controller. It is vitally important that you collect all event data from the controller before changing the address. Once the address is changed (and the RAM is automatically cleared) the event information in the controller is lost and cannot be recovered.
If the address shown as Current needs to be changed, enter the new address by pressing the numbers on the keypad. The number selected will show in the New line. If you enter the wrong number, simply press CLEAR to erase what has been entered. When you are satisfied with the address entered, press *. If you have changed the number from what is shown as current, the controller
will automatically clear the memory after it changes the address.
Once the memory has been cleared, the unit is ready to be configured. The LCD will display a
warning that the unit has not been initialized. This display will rotate with the Entraguard default
display until a Total Update from Doors.NET has been performed on the unit. Once an update
has been performed, only the default will be displayed.
From the Clear Memory Screen you may either:
1. Press 1 to clear the controller’s RAM. The LCD will change to show the memory is being cleared. Once the controller’s RAM has been cleared, the unit is ready for use. The LCD will rotate between the Initialization Warning and Entraguard Default screens until a Total Update from Doors.NET has been performed on the unit.
OR
2. Press 2 to return to the Reset Menu without clearing the controller’s RAM.
Note: Clearing the system RAM completely erases all information within the Entraguard Silver controller, except for the controller address. If there is any information in system RAM from an access control installation and the system RAM is cleared, the information in the controller is lost and cannot be recovered, and a Total Update must be performed.
For information regarding the diagnostics screens and troubleshooting the Entraguard Silver
Controller, see the Entraguard Troubleshooting and Diagnostics Guide (P/N 01912-001).