MR16OUT Module Setup

MR16OUT Module Setup

1.0 Introduction

MR16IN S3


The Authentic Mercury MR16OUT module enables expansion of Authentic Mercury intelligent controllers by offering 16-general purpose outputs as Form C relay contacts. The MR16OUT also provides individually configurable parameters that can be set for timing and for fail-safe versus fail-secure modes.

 

Borealis supports the use of Series 2 MR16OUT modules as well as the new Series 3 enhanced modules - which offer an improved processor, increased memory plus an embedded crypto memory chip that provides a secured layer of encryption to onboard sensitive data.

 

The MR16OUT module can be used for a variety of applications, such as controlling heating/cooling, lighting and controlling doors that do not have access control. You can also use the I/O linkage functionality to control outputs from dedicated general purpose inputs.

 

 

3.0 Configure the RS-485 Address and Baud Rate

The S1 switch on the MR16OUT module is used to set the RS-485 address and the controller's baud rate. The first MR16 module that you add to the bus, by default, will be configured in the software as address 0 and the default baud rate is set to 38,400bps.

 

The S1 switch should have #6 and #7 in the ON position and all other switches are in the OFF position. This configures the controller as address 0 and the baud rate will be 38,400.

 

SW configuration

 

Use the S1 switch to change the RS-485 address (switches 1-5) or the baud rate (switches 6 and 7).

 

Because address 0 is a valid address on the 485 network, the second address will be address 1 (#1 in the ON position), the third module will be address 2 (with switch #2 in the ON position) - as highlighted in the following image.

 

MR Module Address

 

 

The comm address will automatically be set in the software based on the following rules:

 

  • The first module to be added to the controller's bus will be configured in the software as address 0. The second module added will be address 1, and so on.
  • Each of the controller buses can have up to 32 MR16 modules.
  • If you add modules to a different bus, again, the first module will be address 0 (because it will be a second, completely separate RS-485 network).

 

 

4.0 Add the MR16OUT Module in Borealis

  1. From the Borealis main menu, go to Hardware >> All.

    Main menu all

  2. Expand the controller located on the hardware tree.
  3. Select the TB port that the module is connected to.

    Note: Some controllers have 2 x TB ports (TB2 and TB3), whereas other controllers only have 1 x TB port (TB3).

  4. You will see the port properties located on the right-side of the screen.
  5. Click the ADD PANEL button.
  6. Select MR16OUT from the drop-down list.
  7. Click the SAVE button.

    Add MR16OUT

  8. Expand the controller port and then select the new module.
  9. The MR16OUT properties will displayed on the right.
  10. If the module is addressed correctly it should show as online.

    MR16 Online

    • Related Articles

    • MR52 Dual Door Module Setup

      1.0 Introduction The MR52 dual door interface panel with on-board flexibility to connect to a wide range of security devices. The MR52 is easy to install and provides the required I/O for interfacing two card readers, eight general-purpose input ...
    • NXT-MSC - MR16 Module Setup

      MR16OUT-S3 Module MR16IN-S3 Module 1.0 Introduction You can add Mercury MR16IN and MR16OUT modules to the RS-485 port of an NXT-MSC controller after configuring the controller port to the Mercury Security protocol. Each MR16IN or MR16OUT module has ...
    • MR50 Single Door Module Setup

      1.0 Introduction The MR50 Series 3 is an enhanced SIO single card reader interface panel dedicated to individual door oversight and provides all the I/O needed for controlling a single door. Each MR50 connects one card reader, two general-purpose ...
    • MR16IN Module Setup

      1.0 Introduction The Authentic Mercury MR16IN module enables expansion of Authentic Mercury intelligent controllers by offering 16-general purpose input circuits and two-programmable relay outputs. Borealis supports the use of Series 2 MR16IN modules ...
    • System Setup

      Introduction Note: If you are using the new user interface, the instructions can be found here: https://help.kerisys.com/portal/en/kb/borealis/new-user-interface/system-setup This section explains how to setup a new Borealis cloud access control ...