NXT-MSC - MR16 Module Setup

NXT-MSC - MR16 Module Setup


Red MR16OUT       MR16IN Module

 

MR16OUT-S3 Module                                                      MR16IN-S3 Module

 

1.0 Introduction

You can add Mercury MR16IN and MR16OUT modules to the RS-485 port of an NXT-MSC controller after configuring the controller port to the Mercury Security protocol.

 

Each MR16IN or MR16OUT module has 16 inputs or 16 outputs and therefore offers a very cost-effective means of adding multiple general purpose inputs and outputs to the system. The MR16IN and MR16OUT modules can also be used for elevator control.

 

Notes:

  • If you will be using an MR16IN or MR16OUT module then no other device types will be supported on that port (for example; an NXT 4x4 module or an NXT reader).
  • An NXT reader is added to the controller port by default - so before attempting to add an MR module this NXT reader will need to be deleted.
  • Each bus can support up to 32 panels (either MR16IN or MR16OUT or a combination of both). The first controller added to the port will be configured as address 0 in the controller properties.
  • The maximum number of MR modules for an NXT-MSC 2D controller is 64. For an NXT-MSC 4D controller the maximum is 96.
  • Also supports the Series 2 MR16 modules (the green colored boards).

 

 

2.0 NXT-MSC Controller to MR16IN/MR16OUT Wiring

2.1 Wiring at the NXT-MSC Controller

MR Module Wiring

 

 

Important Notes:

You should not power the MR16IN or MR16OUT module from the controller's bus. The MR16IN or MR16OUT module should have its own dedicated power supply.

You should connect the RS-485 shield drain to the earth-ground at the NXT-MSC controller only (to prevent ground loops). The shield drain can connect to the earth at pin 3 of the NXT-MSC controller power connector or the ground lug screw as shown in the above diagram.

 

 

2.2 Wiring at the TB10 connector of the MR16IN/MR16OUT Module

Controller to MR Wiring

 

 

2.3 RS-485 Wiring Specification

  • The recommended cable type for the RS-485 connection (between the NXT-MSC controller and the downstream MR16 modules) is Belden 9501 (or equivalent) - this is a 1-pair shielded, stranded, twisted cable. AWG 24 wire or larger (note that increasing the wire gauge does not increase the total network length) - The total network length is 4,000 feet/1,000 meters.

  • The RS-485 wiring between MR16 modules is a daisy-chain connection.

 

 

3.0 Set the MR16IN/MR16OUT RS-485 Address

The S1 switch on the MR16IN or MR16OUT module is used to set the RS-485 address and the controller's baud rate. The first MR16 module that you add to the bus, by default, will be configured in the software as address 0 and the default baud rate is set to 38,400bps.

 

The S1 switch will have #6 and #7 in the ON position and all other switches are in the OFF position. This configures the MR module as address 0 and the baud rate will be 38,400.

 

SW Configuration

 

Use the S1 switch to change the RS-485 address (switches 1-5) or the baud rate (switches 6 and 7).

 

Because address 0 is a valid address on the 485 network, the second address will be address 1 (#1 in the ON position), the third module will be address 2 (with switch #2 in the ON position) - as highlighted in the following image.

 

S1 Address 2

 

The comm address will automatically be set in the software based on the following rules:

 

  • The first module to be added to the controller's bus will be configured in the software as address 0.
  • Each of the controller buses can have up to 32 MR16 modules.
  • If you add modules to a different bus, again, the first module will be address 0 (because it will be a second, completely separate RS-485 network).

 

This allows you to have MR16 modules on one of the controller buses and other panel types on a different bus. The address scheme is so the other buses are not affected. However, once a bus has been configured for Mercury hardware (MR16IN and MR16OUT modules), these will be the only hardware type that you can add to that bus.

 

 

4.0 Set the MR16IN/MR16OUT RS-485 BAUD Rate

The S1 DIP switch is also used to set the RS-485 BAUD rate to 38,400 (using S6 and S7 in the ON position).

 

MR Baud Rate

 

 

 

5.0 Add an MR16IN or MR16OUT Module

Note:

  • This section assumes you already have an NXT-MSC controller added to Borealis and online.

 

 

5.1 Remove the default Keri NXT reader from the controller's port

  1. In Borealis, from the main menu select Hardware then All.

    Main menu all

  2. All controllers on the system will be displayed on the hardware tree.
  3. Expand the controller that has the module connected to it.
  4. Expand the bus on the controller.
  5. Select the reader which is added to the port by default.
  6. On the right side of the screen click the DELETE button.
  7. The default reader will be removed from the controller port.

 

 

5.2 Configure the Controller Port for the Mercury Protocol

  1. Select the port that the reader was removed from.
  2. Click the EDIT button.

    MR Edit Port

  3. The port edit form will appear.
  4. Set the Protocol to Mercury Security.

    Protocol - Mercury

  5. Click the SAVE button.

 

Note: After changing the controller port's protocol you will need to do a memory reset on the controller. This can be done after adding the MR module(s).

 

 

5.3 Add the MR16IN or MR16OUT module to the Controller Port

  1. Select the bus that the MR16 module is connected to.
  2. On the right side of the screen, click the ADD PANEL button.

    Add Panel button

  3. From the Panel Model selection select the MR16IN or the MR16OUT module.

    Model Select

  4. Click the SAVE button.
  5. The module will be added to the controller's port.
  6. Expand the controller port and select the new module.

    Select new module

  7. The module's properties will be displayed on the right.
  8. The module's status should be Online.


    MR16 Online

    Note: The first panel that you add to a controller port will be address 0. It is important to also ensure the model type is correct. The module will not come online if it is an MR16IN but added as an MR16OUT module.

  9. Click on Hardware >> Panels and you will be able to view all the MR16 modules that have been added.


    MR16 Panels screen


    • Related Articles

    • NXT-MSC Controller Setup

      1.0 Introduction The following steps explain how to add an NXT-MSC controller to Borealis. It assumes that you have already followed the steps to add an NXT-MSC site to your system. During the steps to claim the hub you will select the site that the ...
    • Elevator Control - Using NXT-MSC Controllers

      1.0 Introduction Borealis provides a cost-effective elevator control solution using NXT-MSC controllers with 4x4 modules or MR16 modules and True Mercury controllers using MR16 modules. Elevator control uses a reader on the controller's bus 1 to ...
    • Add an NXT 4x4 Module

      The NXT 4×4 module is added to the system via the controller section. Note: It is not currently possible to link inputs to outputs or re-assign the inputs and outputs to door contact, RTE, strike functionality, etc. Currently, you have the ability to ...
    • MR52 Dual Door Module Setup

      1.0 Introduction The MR52 dual door interface panel with on-board flexibility to connect to a wide range of security devices. The MR52 is easy to install and provides the required I/O for interfacing two card readers, eight general-purpose input ...
    • Configure Door Functionality on an MR16 Module

      1.0 Introduction You can configure an MR16IN and an MR16OUT module with input and output door functions. For example; you can program inputs on the MR16IN to function as the door contact and the RTE inputs. You can also configure an MR16OUT output to ...