This section explains how to enable the standard implementation of the Global Unlock feature using the dedicated Global Unlock input on a Primary PXL controller (controller addressed #1).
The dedicated Global Unlock input is physically located between pins 5 and 6 of TB4 on the PXL controller. This input can alternatively be designated as an Auxiliary RTE input, but this function is automatically disabled when Global Unlock is enabled.
The Global Unlock input is a normally-open input that is active when closed. When the input activates it automatically unlocks all online and functioning doors on the PXL network; it does NOT allow you to select certain doors to not respond to the global unlock command. Since this feature is hardware controlled it is not dependent on the PC in any way.
Notes:
This section assumes you have already followed the steps to get the primary PXL controller online.
Note: Once Global Unlock has been enabled on the controller, the controller will be updated automatically. A network update event will appear in live events.
----------------------------------------------------------------------------------------
Note: The Global Unlock feature is NOT Fire Marshall approved. Check your local codes for fire safety management.
Note: Global Unlock takes precedence over ALL lock or unlock commands. Any attempt to restore an Auto Unlock/Lock time schedule while the Global Unlock feature is active will be ignored by the Primary controller.