1.0 Introduction
This section explains how to setup and configure an LP1501 controller with the Doors.NET software. All LP controllers are pre-configured for use on a network, therefore additional TCP/IP configuration must take place in the field prior to placing each unit into service. The controller is configured using Doors.NET (or you can use a web browser) via a network connection or cross-over cable. The following steps explain how to connect to the LP1501 controller over a network.
Notes:
- The following setup instructions assume that Doors.NET has already been installed and you already have the MSC gateway setup and online.
- For extended and advanced controller settings please refer to the LP Controller Full Configuration document.
2.0 Factory Default Communication Parameters
- Network: static IP address: 192.168.0.251
Subnet Mask: 255.255.0.0
- Default Gateway: 192.168.0.1
DNS Server: 192.168.0.1
- Host port: IP server, no encryption, port 3001, communication address: 0
3.0 Factory Default DIP Switch Setting
The state of the switches on the controller determines the user information used for log on authorization, and communication parameters. By default you would set the DIP switch so that the controller uses factory default communication parameters (this gives the controller a static IP if 192.168.0.251).
Caution: In the factory or OEM default modes, downloaded configuration/database is not saved to flash memory.
Switch | Definitions |
1 | 2 | 3 | 4 | |
OFF | OFF | OFF | OFF | Normal operating mode. |
ON | X | OFF | OFF | After initialization, enable default User Name (admin) and Password (password). The switch is read on the fly, no need to re-boot. See IT security for additional information. |
OFF | ON | OFF | OFF | Use factory default communication parameters.(Address: 192.168.0.251 Port: 3001). |
ON | ON | OFF | OFF | Use OEM default communication parameters. Contact system manufacturer for details. See Bulk erase configuration memory. |
ON | ON | OFF | OFF | Bulk Erase prompt mode at power up. See Bulk erase configuration memory. |
X | X | X | ON | Makes the LP1501 report and function like an EP1501. To be used in situations where the host software has not been updated to support the LP series product line. |
- The material provided describes the behavior of the browser with the factory default settings.
- The look and feel of the of the web interface will vary depending on the OEM Settings. Many settings made in the browser can have an OEM specific default. Items that can be customized are in notes.
If the controller is using the factory default settings and has the default IP address of 192.168.0.251, you will have to configure the host PC with an IP address on the same range as the controller default IP. Once the controller is online in Doors.NET you can then configure the controller with the IP address that you wish the controller to use.
- Go to Windows Control Panel.
- Select Network Sharing Center.
- Click on Change Adapter Settings.
- Right-click the adapter for your Local Area Network and select properties.
- Select Internet Protocol Version 4 (TCP/IPv4).
- Click the PROPERTIES button.
- Select 'Use the Following IP Address'.
- Configure the PC with the same settings as the controller's factory settings (except the IP address should be different).
- Open a command prompt and verify that you can ping the controller's default IP address (192.168.0.251). Expect the IP address to reply successfully.
5.0 Add the Controller to Doors.NET
You can now add the controller to the Doors.NET software and then log into the controller's configuration to set it to a static IP address. This section assumes you have Doors.NET already installed and licensed and you have an MSC gateway setup and online.
- Log into the Doors.NET software.
- Go to Setup >> Hardware Setup >> All to display the hardware tree.
- Select the MSC gateway (located at the top of the hardware tree).
- Click the SCAN NETWORK button.
- The MSC gateway will scan the Local Area Network and will display any detected controllers, including the LP-1501. It should also be displaying its default IP address.
- Select the LP-1501 and click on the IMPORT button.
- Click YES to proceed with the import then OK to confirm the import.
- Return to the hardware tree and you will see the controller now listed beneath the MSC gateway.
6.0 Manually Add the Controller to Doors.NET
If the controller has been configured via a web browser and you know the controller's MAC address, then you can manually add the controller to Doors.NET and enter the controller's MAC address. The IP address will be automatically assigned once the controller is online.
- In Doors.NET go to Setup >> Hardware Setup >> All.
- The MSC gateway will be displayed at the top of the hardware tree.
- Select the MSC gateway.
- Click on the LP Series icon from the Mercury Security hardware group.
- Enter a description for the controller.
- Select the specific controller type from the Model drop-down list.
- Enter the controller's MAC address.
- Click the ACCEPT button.
- The controller will be added to the hardware tree.
- The controller will come online almost immediately.
- Select the newly added controller (from the hardware tree).
- The controller properties will be displayed on the right.
- In the Communication Settings section you will see that the controller's IP address is automatically detected and added to the controller properties.
7.0 Set the Controller With a Static IP Address
If the controller has its default, static IP address (192.168.0.251), or if you wish to change the controller's IP address, you should now enable 'Design Mode' to log into the controller's internal configuration and to change the controller to a preferred static IP address. You can also log into the controller using a web browser. Using Doors.NET however, is the easiest and preferred method and avoids any possible browser security restrictions or limitations.
Notes:
- Logging into the controller's internal configuration will allow you to access several advanced controller settings. All these additional settings are explained in the LP controller Full Reference Guide.
- You cannot change the controller's configured IP address simply by changing the address in the controller properties.
- Close the hardware setup page.
- Click the Design Mode icon (located in the upper-left).
- When Design Mode is enabled the client will state 'Design Mode' in the title bar.
- Re-open the hardware setup page.
- Right-click the controller and select Internal Controller Configuration.
Note: There are many other settings in the Internal Controller Configuration - these are all explained in detail in the LP
- From the web-page drop-down menu, select Network then click the refresh icon.
- The controller's IP settings will be displayed on the right.
- Set the network method to static.
- Enter the specific static IP address that you wish to assign to the controller.
- Save the controller's internal configuration.
- Click the APPLY and REBOOT button.
- Click YES to confirm.
- Close the internal config window.
- The new static IP address will be assigned, the controller will reboot and the controller will then show as offline (because the host PC will now be on a different IP range).
- Now, go back to Windows Control Panel >> Local Area Network settings and set the host PC IP address to an IP address in the same range as the controller's new static IP address.
- Down-power the LP-1501, set the S1 DIP switch the following: 1 - OFF 2 - OFF 3 - OFF 4 – OFF - this configures the controller for normal operation.
- Apply power to the controller, wait approximately 10 seconds for the controller to completely boot up, it should then be showing in Doors.NET as online.
- Controller online events will be generated and displayed in live events.
- Exit the hardware setup screen and exit Design Mode.
8.0 Upgrade the Controller Firmware
If you see a 'Controller Firmware Needs Upgrading' event when the controller initially comes online then you will need to perform a firmware upgrade. The most up-to-date firmware file is included when you install the software.
- Select the new controller from the hardware tree.
- Click the firmware upgrade icon in the ribbon bar.
- The firmware upgrade directory will open and the most up-to-date firmware file will be displayed.
- Select the new firmware file and click OPEN.
- You will see a warning message that the controller will momentarily go offline during the upgrade. Confirm this message then click OK.
- The entire controller upgrade should be completed in approximately 60 seconds.
- When you see the Firmware Upgrade Complete message in live events, go to the controller status grid and the new firmware version will be displayed.