Neutron Controller Specifications

Neutron Controller Specifications

Small Enclosure Size:
2.75” H x 4.25” W x 1.32” D

Full Kit Enclosure Size:
7.25” H x 6.6” W x 1.8” D

PC Board, No Enclosure Size:
2.36” H x 4.0” W x 0.78” D

Input Voltage:
+ 12 VDC nom. (9-15 VDC)

Current Draw:
NEUT Controller - 250mA

Inputs (2):
Door Contact Switch
Request to Exit

Outputs:
1.0 amp (24 VDC max.)
dry circuit

Reader Capacity:
2 (using NXT Readers)*
NXT 3R or 5R
NXT 3RE or 5RE

Buffer Capacity:
4,000 offline

Temperature / Humidity:
-40°F to 140°F
(-40°C to 60°C)


Communication:
RS-485 (A minimum of one
Neutron Communication
Cable Kit is required per
installation.)


Lithium Battery:
5 years Memory Retention

RS-485 Cable Requirements

RS-485 bus runs can daisy-chain together an NXT-4x4 and NXT-Reader on one line. The total cable run distance should be no more than 500 feet from the Neutron controller for runs with 4x4s and no more than 1,000 feet for reader-only runs.


Connection


Run Length


Purpose


Conductors


Shielded


Stranded


Twisted Pair


AWG


RS-485 from Neutron controller to NXT 4x4 (with or without an NXT 1R/3R/5R reader)



Up to 500 feet (150 meters)


Power



2


N


Y


N


18

Data

2
Y
Y
Y
22 or 24


RS-485 from Neutron controller to NXT 1R/3R/5R readers


Up to 1,000 feet (300 meters)



Power


2


N


Y


N


18

Data

2
Y
Y
Y
22 or 24


Controller Power, Inputs, and Outputs Cable Requirements

Connection
Total Run Length
# of Conductors
Shielded
Stranded
AWG
Controller Power
250 feet [a]
2
N
Y
18
Earth Ground
Shortest path [b]
1
N
N
18
Inputs and Outputs [C]
500 feet
2
N
Y
22
  1. To meet CE and C-tick regulations, the length of the controller power line can be no longer than 3 Meters (9.85 feet).
  2. Use the shortest possible path from earth ground point to PCB. Connect the earth ground only to the designated pin on the terminal block. This is important as all transient protection for the unit is made through this earth ground connection. For unit protection, the earth ground connection should always be made first.
  3. Values listed are minimums. Individual input and output devices may have more specific requirements.

Notes: 
  1. The Lock Output relay may require a heavier gauge of wire depending upon the current demands of the lock and the length of the lock wiring run.
  2. Cable resistance causes a drop in voltage at the end of long cable runs. Ensure the appropriate power and current for your device is available at the device at the end of the cable run. Heavier gauge cable reduces this effect.
  3. Keri does not recommend hot-plugging a Reader, RIM, or 4x4 into an Neutron controller. Remove power from the controller prior to connecting these devices.

USB Adapter to PC Extension Cable

A USB extension cable can be used to extend the connection between the PC and the USB adapter - this cable should be a maximum length of 20 feet.

    • Related Articles

    • Neutron Introduction

      1.0 Introduction Neutron is a single-door controller which is configured and managed using Keri's Visual Doors software. It is a small, low-cost, easy to install controller that supports 1 or 2 NXT readers (1 x entry and 1 x exit reader) and is ...
    • Neutron Data Sheet

      Neutron Controller Data Sheet
    • Neutron Hardware Installation Guide

      1.0 Introduction Neutron a single-door controller type which is configured and managed using Keri's Visual Doors software. It is a small, low-cost, easy to install controller that supports 1 or 2 NXT readers (1 x entry and 1 x exit reader) and is ...
    • Neutron Controller Setup in Visual Doors

      1.0 Software Installation Notes When performing the Doors.NET installation, you should select the Full Installation (this installs all software components for a standard installation onto the PC, including the Neutron gateway). Alternatively, if you ...
    • Neutron Controller LED and Jumper Definitions

      LED and Jumper Definitions (See Neutron controller diagram for location of the LEDs and jumper) J2 (TAMPER): Provides a normally-closed tamper input to the controller. D15 (PWR FLT): Indicates a short on the controller or if the power lines are ...